Code: Seba-KMT VLF-CR-20
Description
VLF CR-20
In accordance with most regulations, cables and joints must be tested after installation or repair. For this test the breakdown strength of the cable is tested.
The portable VLF Test System 20 kV of Seba KMT can be used to test the cables in conjunction with the according local regulations for operating voltage levels up to 11 kV for new cables and 16 kV for aged cables at 3 µF cable capacity.
By using the patented Seba KMT 0.1 Hz Cosine Square Wave Voltage, weak and for further operation critical spots in PE, XLPE but also in paper cables are brought to a controlled breakdown very fast without causing additional damage or ageing to the cable insulation.
The weight of 50 kg make the VLF Test System 20 kV a powerful, universal and at the same time portable unit.
_ The patented change over principle in combination with
the recycling of energy stored in the cable capacity
results, in comparison to other methods, in a lower
weight, less energy consumption and much higher test
capacity.
_ The high test capacity of 3 µF permits the simultaneous
testing of all three phases.
_ The method is officially recommended by the two VDE
Standards 0276-620 and 0276-621.
_ Independent researches shows that VLF test is done
most effectively with the 0.1 Hz cosine square wave
shape compared to any other VLF wave shape or
frequency.
_ VLF is the most economic method for testing PE and
XLPE cables. DC test is not applicable for these cable
types.
_ controlled output voltage
Standard accessories
Scope of Delivery
_ Basic unit
_ AC mains cable
_ Earthing cable 4 m
_ HV-connection cable 4 m
_ Accessory bag
_ Operating manual
Recommended options
Options
_ Breakdown recognition and automatic shut-down.
_ VLF / DC leakage current measurement
More products SEBAKMT
|
SEBA KMT LPD MONITOR ON-LINE PD PARTIAL DISCHARGE MONITORING SYSTEM FOR MV AND HV
• Portable online PD measuring system for monitoring MV and HV systems |
|
SEBA KMT GEOLUX GL 660-1 EARTH FAULT LOCATOR FOR FAULT LOCATION IN ISOLATED, EARTH FREE SYSTEMS
• Earth fault locator for fault location in isolated, earth free systems |
|
SEBA SMART THUMP 16 CABLE FAULT LOCATION SYSTEM ON LOW AND MEDIUM VOLTAGE CABLES
• 1500J at 8 / 16 kV, 16 kV DC-HV proof test 23/46mA Burning |
|
SEBA TELEFLEX T3060 SINGLE-PHASE POWER CABLE REFLECTOMETER T 3060
• Range 8 km, 64 km (for ICE and Decay only) |
|
SEBA KMT HPG 50..80-D DC & AC HIGH VOLTAGE CABLE TESTER
• HPG 50-D, AC testing up to 35 kVRMS/ DC testing up to 100 kV |
|
SEBA KMT HV TESTER 25KV HIGH VOLTAGE DC TESTER
• DC output voltage of 0 - 25 kV |
|
SEBA TELEFLEX SX CABLE REFLECTOMETER FOR FAULT LOCATION MEGGER
• ARMslide technology with 15 traces in one ARM shot |
|
SEBA KMT HPA35 HPA50 HPA58 HPA78 AC HIGH VOLTAGE HIPOT TESTING WITHSTANDING
• HPA 35, AC testing up to 35 kVrms |
|
SEBA KMT EASYTEST 20KV VFL CABLE TESTER VERY LOW FREQUENCY
• simplified version of the standard VLF test |
|
SEBA KMT VLOCML2 PIPELINE LOCATION AND TRACING FOR UNDERGROUND PIPES AND CABLES
• Location of passive markers which are used by utility |