Seba KMT OWTS M60 Dielectric Diagnosis and Partial Discharge Measuring System

Code: Seba-KMT OWTS-M60


 

Datasheet PDF, 0.31 Mb
 

Description

OWTS M60

Dielectric Diagnosis and Partial Discharge Measuring System

The oscillating wave test system OWTS is used to identify, evaluate and locate partial discharge (PD) faults in a cable insulation and in joints and terminations.

The HV unit generates the attenuated oscillating frequency up to the peak v oltage of the system. An Embedded controller for the operation and the digital signal processing and storage from two 100 MHz AD converter systems is intergrated in the cylindrical  housing. Transport wheels permit easy transportation. The communication to the user interface of the notebook is done by W-LAN. Optional a optical data link is possible.

The OWTS can also be coupled with a VLF System. In this case the VLF provides, controlled by the OWTS, the High Voltage supply.

 

Key Benefits:

  • PD diagnosis under oscillating wave test voltage - electrical field distribution as in nominal service conditions
  • PD evaluation possibility and pattern recognition at the nominal voltage level
  • Automatic Calibration and Joint location facility
  • PD level measurement according to IEC 270 at a bandwidth of 150 ... 650 kHz
  • Semi- and fully automatic PD analysing software for defect location with mapping feature
  • Calculation of the cable capacitance and the tan delta value of the test object from the characteristic decrease of the voltage wave shape
  • Simple to use and easy to handle menu-driven unit for operation of the test sequence
  • Compact design; low weight
  • Compact PD: combination of OWTS, vlf test unit and the fault location system Compact

 

 

 

Standard accessories

Scope of delivery

?? HV unit

?? Notebook with WLAN connection to the HV unit

?? Safety-Box with HV ON/OFF; Emergency push button

and key switch

?? Accessory bag

?? Operating manual

?? 5 m HV test lead; power supply and grounding cable

?? OWTS Explorer package, 2 Dongle CD-ROM

?? Calibrator

?? Additional capacitor

 

Recommended options

 

 

More products SEBAKMT

SEBA KMT HV TESTER 25KV HIGH VOLTAGE DC TESTER

• DC output voltage of 0 - 25 kV
• Portable HV Tester
• DC and insulation testing of cables, joints, electrical fixtures, etc.
• High flexibility with built-in battery

 

SEBA KMT HVB-10 10KV CABLE FAULT LOCATION, STEATH TESTING AND PINPOINTING MEGGER HVB10

• Output voltage 0 … 10 kV DC, bi-polar
• Automatic test sequence
• Bi-polar prelocation for the elimination of external influences
• Detection and indication of wrong connections
• Touchscreen and rotary encoder
• Only one HV connection cable
• Completely independent of the parameters of auxiliary lines

 

SEBA SWG 505 SURGE WAVE GENERATOR FOR FAULT LOCATION IN CABLES SWG505

• Voltage Ranges : 0.. 3kV / 4kV / 5kV
• Energy : 180J / 320J / 500J
• MAx Current Imax : 129mA / 182mA / 213mA
• Optimized surge energy for switchable capacitors
• ICE - Impulse Current Method
• ARM - Arc Reflection Method

 

SEBA KMT EASYTEST 20KV VFL CABLE TESTER VERY LOW FREQUENCY

• simplified version of the standard VLF test
• Easy to operate
• Configurable test sequences
• Compact, rugged and lightweight design
• AC, DC and sheath testing in one single system
• Reporting via USB or Winkis

 

SEBA KMT EASYLOC CAM LOCATION SYSTEM FOR LOCATION AND DEPTH MEASUREMENT OF SEWER TV CAMERAS

• 3 active frequencies (512 Hz, 640 Hz und 33 kHz)
• depth measurement at the push of a button
• Maximum marker to mark the strongest signal
• optional: Carry Bag - for easy and safe transport of Easyloc Cam
• optional: Pipeline sonde - for location non-metallic pipes

 

SEBA KMT VFL CR-60-HP LONG CABLES TEST SYSTEMS

• Very high test power without frequency reduction
• Covers cables up to 20 km @ maximum Voltage
• No polarisation effects as with DC
• Protocoling
• Breakdown detection
• Leakage current measurement
• Powerful 0.1 Hz VLF test system with energy recovery

 

SEBA KMT HV TEST SET 50KV 80KV 110KV DC HIGH VOLTAGE TESTER

• available in three versions: 50kV 80kV 110kV DC
• Highest safety by monitoring functions and easy operation
• Quick and easy mounting with compact and simple setup
• Meeting individual needs by modular design

 

SEBA KMT OWTS M28 PARTIAL DISCHARGE TEST AND FAULT LOCATION SYSTEM IN CABLE INSULATION

• PD Measurement by means of DAC similar to nominal net frequency
• Online processing for complex PD-Diagnosis
• Portable test system, compact design and low weight
• Integrated tan d - measurement

 

SEBA KMT FERROLUX FLE 10 AUDIO FREQUENCY RECEIVER FOR CABLE LOCATION, SELECTION, SHEATH FAULTS

• Precise direction guidance with right/left arrows
• "SignalSelect" for clear route location
• Depth and signal current intensity measurement at the push of a button
• Route sensor weighs less than 1 kg for non-tiring use
• "DirectSignal" for effective line location

 

SEBA EASYFLEX COM REFLECTOMETER LOCATE FAULTS ON CU TELECOMMUNICATION, SIGNAL AND POWER CABLES

• Test range 50 m ... 15000 m
• High local resolution of 5 cm in 50 m test range
• Simple operation due to menu prompting and help functions
• Easy evaluation of the traces by simultaneous display of zoom and total view (split-screen)
• Large display with backlight
• Individual measurement, continuous measurement and averaging
• Measuring connections suitable for live voltage up to 250 V