dry-contact inputs 3 dry-contact channels
-
each channel detects main contact and insertion resistor contact
-
timing windows 1 second, 10 seconds, or 20 seconds
-
timing resolutions ±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration
-
breaker operations Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
-
Stand-alone, microcomputer-driven EHV Circuit Breaker Analyzer
-
Analyzes contact time, stroke, velocity, over-travel, and contact wipe
-
USB PC interface
-
USB Flash drive interface
-
Can store up to 200 test records and 100 test plans
-
Built-in thermal printer
The Vanguard DIGITMR S2 is an inexpensive, easy to use digital circuit breaker analyzer. The DIGITMR S2 can be operated stand-alone or can be computer-controlled. It can fully analyze a circuit-breaker’s performance by testing the contact time, stroke, velocity, over-travel, and contact wipe. Contact and motion analysis can be performed for all breaker contact operations (Open, Close, Open – Close, Close – Open, and Open – Close – Open). Timing results are recorded and displayed on the 240 x 128 pixels back-lit LCD screen and can also be printed on the built-in 4.5" wide thermal printer.
Contact Timing Inputs
Dry-contact input channels are used for timing
circuit-breaker contacts. Each contact input
channel can detect main contact and insertionresistor
contact times in milli-seconds and cycles.
Three contact timing channels are available
on the DIGITMR S2.
Breaker Stroke and Velocity
One digital transducer input channel is available
to measure circuit breaker contact stroke,
velocity, over-travel, and bounce-back. With the
use of a Vanguard digital travel transducer, no
set-up calibration is required before testing. A
special feature is also available to “Slow-Close”
test a circuit breaker and obtain test results. An
optional Resistor Transducer Adapter Device can
be used to interface with any resistor transducer.
Built-in Thermal Printer
The DIGITMR S2 features a built-in 4.5” wide
thermal printer that can print test results in both
tabulated and graphic format.
Voltage Monitoring Input
One analog input channel, designated as (V1), is
dedicated to monitoring the substation DC supply
or coil voltage (0-255 Volts, DC or peak AC).
A second voltage input channel, designated as
V2, is dedicated to detecting voltage On/Off
status (presence or absence). This input can be
used to monitor the status of an A/B switch.
Circuit Breaker Initiate Feature
A built-in solid-state initiate device is used to
operate the circuit breaker from the DIGITMR
S2. Operational modes include Open, Close,
Open-Close, Close-Open, and Open-Close-
Open. Multiple operations such as Open-Close,
Close-Open, and Open-Close-Open can be
initiated using a programmable delay or by
sensing the circuit breaker’s contact condition.
The circuit breaker coil current amplitudes and
waveforms are recorded and can be printed on
the thermal printer.
Computer Interface
One USB interface port and one optional Bluetooth
interface is available for computer-control. Vanguard's
Windows®- based Circuit Breaker Analyzer application
is included with each DIGITMR S2. The software can be
used to control the unit, review test records, and create
circuit breaker test plans. Test records can be exported
to PDF, Excel, and XML format. All future software updates
can be downloaded from the Vanguard web site at
no additional charge.
User Interface
The DIGITMR features a back-lit (256 x 128 pixels)
graphic LCD screen to display menus and test results.
A convenient, rugged, 44-key QWERTY-style keypad is
used to control the unit and enter data.
CT Input
One non-contact AC current sensor is used to
monitor circuit breaker on-line current for the
“on-line” timing mode.