Auto discharge circuit for operator safety
-
3 resistance reading channels including one dynamic channel
-
Digital resistance reading from 1 micro-ohm to 500 ohms
-
Calculate equivalent resistance value at reference temperature
-
Stores 50 static records and 20 dynamic records
-
Built-in 4.5-inch thermal printer
-
Weighs less than 44 lbs.
The LTCA-10 Analyzer is a second generation load tap changer analyzer. The LTCA-10 accurately measures winding resistance of highly inductive power transformers. Triple resistance-reading channels allow the measurement of three winding resistances simultaneously. Four-wire (Kelvin) connections provide high accuracy and require no lead compensation. A special feature of this device is its ability to measure and graph the resistance trace of a transformer LTC during operation. Using a 60Vdc power supply, the LTCA-10 is capable of outputting 10 amperes.
Transformer Load Tap Changer
Control
Transformer tap positions can be changed remotely using
the unit’s built-in transformer load tap changer. This
remote-controlled tap changer feature eliminates the
need to manually change a transformer’s step-up and
step-down taps.
Resistance Reading Features
Three resistance-reading channels can measure resistance
from 1 micro-ohm to 500 ohms, and the test
current is programmable (1A, 5A, 10A). The LTCA-10
can also be used to measure EHV circuit-breaker contact
resistance, motor winding resistance or any low
resistance. If the transformer winding temperature is
entered, the LTCA-10 can calculate the equivalent resistance
value of the winding material (aluminum or copper)
at any standard reference temperature. Also, a special
test mode can run a test for up to 45 minutes while
saving resistance readings at one-minute intervals.
AC Motor Current Monitoring
One AC current monitoring channel is dedicated
to monitoring the LTC voltage regulator motor
current during operation. The motor current is
also printed on the resistance graph and can
help detect LTC voltage regulator motor problems.
An AC clamp-on current sensor is provided
with the LTCA-10.
Built-in Safety Features
At the end of each test, the LTCA-10 automatically
dissipates the stored energy in the transformer.
This discharge circuit will continue to
work even if the supply voltage is lost.
Dynamic Resistance Test
Features
One resistance reading channel is dedicated to
dynamic resistance testing. This test can monitor
the LTC voltage regulator contact resistance
during operation. A resistance graph, plotting
resistance over time, can be printed on the builtin
thermal printer and is very useful for detecting
LTC voltage regulator contact problems.
Built-in Thermal Printer
The built-in 4.5-inch wide thermal printer can
print the breaker contact analysis results in both
tabular and graphic formats.