Highest ratio: 0.8 - 15,000
-
Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC, and Australian standards
-
3 Test voltages available: 8Vac, 40Vac, 100Vac
-
Phase angle and excitation current measuring
-
Computer Interface (RS-232C and USB Port)
-
USB flash drive interface
-
Name-plate turns ratio calculation
-
Computed % error based on measured and calculated ratio
-
Optional 4.5" thermal printer
-
Powered from a single phase 100-264 Vac 50/60 Hz
The Vanguard Instruments ATRT-03 S2 is the third generation, microprocessor-based, automatic, three phase, transformer turns-ratio tester. This light weight, rugged, portable unit is designed for transformer testing at utility power substations.
The ATRT-03 S2 determines the transformer turns ratio using the IEEE C57.12.90 measurement method. The ATRT-03 S2 outputs an excitation test voltage to the transformer primary windings. The induced secondary voltage is sensed and the transformer turns ratio is calculated. The ATRT-03 S2 is capable of measuring turns ratios from 0.8 to 15,000. The transformer turns-ratio, excitation current, and phase angle readings are displayed on the large LCD. The automatic transformer type detection feature allows the ATRT-03 S2 to detect and test 130 transformer types defined by ANSI, CEI/IEC and Australian standards.
The ATRT-03 S2 can be used as a standalone
unit or can be computer-controlled. It can be
operated locally using its alpha-numeric keypad
and rotary switch. Information is displayed
on a back-lit LCD screen (128 x 64 pixels) that
is viewable in both bright sunlight and low-light
levels. Test reports can be printed in the fi eld on
the unit’s built-in 4.5-inch wide thermal printer.
The ATRT-03 S2 is capable of storing up to 112
test records and 128 test plans in Flash EEPROM
memory. Test records or test plans can be stored
or transferred to and from a PC via the available
interfaces (RS-232C port, USB port, USB Flash
drive port).
Transformer Test Voltages
To prevent an accidental wrong test-lead hookup
(e.g., when the operator reverses H and X
leads), the ATRT-03 S2 outputs a low-level test
voltage to verify the hook-up condition before
applying the full test voltage to the transformer.
Three test voltages (8 Vac, 40 Vac, 100 Vac) allow
the ATRT-03 S2 to test CT’s and PT’s, as well
as power transformers.
Auto-Detect Transformer
Confi guration
The ATRT-03 S2 can automatically detect 130
specifi c vector groups for different transformer
types defi ned by ANSI, CEI/IEC, and Australian
standards.
Internal Test Record
Storage
Up to 112 test records can be stored in the ATRT-
03 S2’s Flash EEPROM memory. Each test record
may contain up to 99 turns-ratio, excitation
current, phase angle and nameplate voltage
readings. Test records can be recalled locally or
transferred to a PC via the available interfaces
(RS-232C port, USB port, USB Flash drive port).
Transformer Test Plans
The ATRT-03 S2 can store up to 128 transformer
test-plans in its Flash EEPROM. A test-plan is
comprised of the transformer nameplate voltages
for each tap setting. The calculated turnsratio
based on the nameplate voltages is compared
with the measured turns-ratio to derive
the percentage error and Pass/Fail results. By
using a test plan, a transformer can be quickly
tested and turns-ratio Pass/Fail reports can be
reviewed. Test plans can be created with the PC
software and can be transferred to the ATRT-03
S2 via the available interfaces (RS-232C port,
USB port, USB Flash drive port).