The Circuit breaker analyzer system is widely used to test live tank oil, bulk-oil, vacuum, SF6 and other models, with different voltage level of high voltage circuit breaker, can also be used for opening and closing & contemporaneous performance of the low-voltage electrical appliances such as contactors and relays.In accordance with IEC standards IEC 62271-100:2008 High-voltage switchgear and control gear - Part 100: Alternating-current circuit-breakers.
(1) No need to choose sensors, a universal sensor can meet all models of circuit breaker mechanical properties testing.
(2) The unique universal bracket with new fixture make it more convenient to acquire the speed signal, there are various models of circuit breakers special bracket, make the measurements more accurate.
(3) Only one kind of connection with different testing methods, simple to use.
(4) Powerful printing can print time data, the time fracture surface curve, time - speed curve, time - stroke curve and stroke - speed curve to facilitate the definition of the speed characteristics of circuit breakers at any time or any stroke.
Power Supply |
Voltage : AC220V±10% Frequency : 50Hz±1Hz |
Executive Standard |
IEC 62271-100:2008 High-voltage switchgear and control gear - Part 100: Alternating-current circuit-breakers |
Dimensions |
Length330mm*Width260mm*Height200mm |
Weight |
5kg(Exclude accessories ) |
Security |
Insulation resistance : >2MΩ |
Leakage Current : <1.000mA |
Dielectric Strength: Power connection line on the shell can withstand 1500V (50Hz RMS) 1 minute. |
Service condition |
Ambient temperature : -10℃~40℃ |
Measurement Accuracy |
Time: ±(1%×reading +0.2ms) |
Speed: ±(1%×reading+0.5m/s) |
Stroke : ±(1%×reading+0.2mm) |
Built-in operation power supply |
DC30~250V Adjustable, instantaneous 20A |