» Specificatii tehnice

 This device is applicable to the test of no-load & load & capacity of 30 ~ 2500kvA distribution transformer under the high current. At the same time in the absence of an external AC power conditions, the instrument provides an internal low-voltage three-phase sine wave inverter testing power supply, transformer capacity can be tested.In accordance with IEC standards IEC 61010-1. Safety requirements for electrical equipments  used in measurement, control and laboratory.

 

 (1) Carry on no-load & load test of 302500KVA transformer under high current; After the load test, it can carry on the judgment of transformer capacity and transformer type.
  (2) Transformer capacity can be automatically tested through the internal testing power supply.
  (3) To facilitate the measurement, it can be used for the testing of transformer capacity in the non-rated tap.
  (4) Instrument can determine power transformers capacity of a full range , S2, S7, S9, S11 type 10KV and 35KV voltage level and so on, and can determine 10KV level 630 ~ 6300KVA high voltage power transformers and the anti-high-voltage power transformers.
  (5) Save 15 transformers of rated capacity to judge the results and no-load, load test records and parameters, power down is not lost.

 

 

Operating Voltage

  Voltage : AC187V-242V,   Frequency : 50±1Hz

 Executive Standard

  IEC 61010-1. Safety requirements for electrical equipments used in measurement, control and laboratory.

 Rated operating conditions

  Ambient temperature : -10-40   Relative humidity : ≤ 85 %

 Dimensions

  415×290×190 (mm)   

 Instrument weight

  about 13 kg

 Capacity measurementRange

  6-11/0.4kV    Power Transformer : 30 ~ 2500 kVA

  6-11/3~6.3kV   Power Transformer : 630 ~ 6300kVA

  35kV             Power Transformer : 50 ~ 31500 kVA

  60-66 kV         Power Transformer : 630 ~ 63000kVA

  110kV             Power Transformer : 6300 ~ 80000 kVA

  S2 Type              Power Transformer : 10 ~ 1800 kVA

  SG Type/10kV Level       Epoxy resin transformer : 30 ~ 1600 kVA

  SGType/35kV Level       Epoxy resin transformer : 50 ~ 31500 kVA

  DType               Single phase transformer : 5 ~ 160kVA

  6 ~ 110 kV Level      Special-type Transformer : 30 ~ 63000kVA

 Voltage range

  0~750V (RMS) Error < ±(0.2%U+3digits)

 Current range

 0~100A (RMS) Error < ±(0.2% I +3digits)

 Power Measurement

  COSΦ = 0.5 ~ 1.0 Error < ±(0.5% P+3digits)

  COSΦ = 0.2 ~ 0.5 Error < ±(1.0% P+3digits)

 