TE2050 Transformer No-load & Load Characteristic Tester is in accordance with national standard GB1094 "Power Transformers" requirements. With many year experience in transformer testing, adopts advanced AC synchronous sampling and automatic calibration technology, we introduce the pragmatic Transformer No-Load & Load Characteristic Tester. The instruments have precise measurement, data stability, data processing automation characteristics. Measurement system has a friendly interface, all English menus prompt, simple and easy to manipulate.In accordance with IEC standards IEC 61010-1. Safety requirements for electrical equipments used in measurement, control and laboratory.
(1) Carry on transformer no-load test, load test, transformer no-load test can automatically capture test data on the set points.
(2) Automatic range switching, and can join CT, PT large transformers’ measurement, all the measured data show the value of direct reading.
(3) The instrument automatically converted the results to 75 ℃.
(4) The instrument with software calibration function can auto-calibrate voltage, current, power and phase.
(5) The instrument with real-time clock, to record test time at any time.
(6) 18 experimental data can be stored, when power-down is not lost, can check at any time.
(7) Test results can be stored to the data card, through special data communications device read into the PC and form test report automatically.
(8) Test results can be printed on site.
Executive Standard |
IEC 61010-1. Safety requirements for electrical equipments used in measurement, control and laboratory. |
Current measuring range |
0-55A Extended type : 0-100A |
Current measurement accuracy |
±(0.2% + 3digits) |
Voltage measurement range |
0-550V Extended type :0-750V |
Voltage measurement accuracy |
±(0.2% + 3digits) |
Power measurement accuracy |
±(0.5% + 3digits) |
Instrument Dimensions |
420×300×220(mm) |
Instrument weight |
about8.4 kg |