Battery Impedance Tester Megger - BITE2 and BITE2P

Code: Megger - BITE2 and BITE2P


 

Datasheet PDF, 1.24 Mb

Description

The BITE2 and BITE2P battery impedance test equipment determine the condition of lead-acid and nickel-cadmium cells up to 7000 Ah. An advanced feature set has been developed that includes Pass/Warning/Fail calculations based on a user-entered baseline value, advanced printing functions and more. The case of the BITE2P consists of both the transmitter and a carrying case for all of the standard accessories and some of the optional accessories, in an all-in-one unit. The BITE2 and its accessories fit into a sturdy canvas case with a shoulder strap.

 

The instruments work by applying a test current across the battery string while on-line, then measuring the total current (ac ripple + test current) and the voltage drop of each cell/jar. It then calculates the impedance. They also measure dc voltage and interconnection (strap) resistance to help determine the overall condition of the entire battery string's electrical path from terminal plate to terminal plate.

 

The BITE2 and BITE2P receiver stores the readings in its internal memory. These measurements, along with other maintenance data such as ambient and pilot cell temperatures and ac ripple current, assist in determining the overall condition of battery systems. Megger recommends that impedance measurements with the BITE2 or BITE2P be made part of a battery maintenance program with readings taken and recorded semiannually for flooded batteries and quarterly for VRLA.

 

Unlike load cycle testing that involves substantial downtime and repeated discharges, using the instruments require no battery discharge, nor do they stress the battery in any way compared to other techniques. With a test time of less than 20 seconds for each cell and intercell connector, one person can easily, quickly, and precisely measure internal cell impedance, dc terminal voltage and intercell connection resistance without taking the battery system off line.

 

Naturally, everything you need to perform these tests is included with the basic instruments. There is a full line of optional accessories to enhance the capabilities of the BITE2 and BITE2P. Both have the ability to download to a PC for data interpretation. Additionally, the BITE P has a built-in printer to review the active test but also to leave a hard copy record at the site.

 

Features:

  • Determines condition of lead-acid and NiCd cells up to 7000 Ah
  • On-board Pass/Warning/Fail indications
  • Robust, repeatable instruments
  • On-line testing
 

More products MEGGER

MEGGER TPT420 VOLTAGE TESTER CATIV 1000V

• CAT IV/1000 V
• IP64 Rated
• 12 to 1000 V AC
• 12 to 1500 V DC
• Continuity test function with visual and acoustic indication
• Voltage indication with no batteries
• Single-pole voltage test
• Phase rotation indication
• Integrated torch light

 

MEGGER MIT200 MIT210 MIT220 MIT230 INSULATION CONTINUITY TESTER

• Pocket-sized insulation and continuity testers - MIT210, MIT220, MIT230
• Insulation testing to 1000 MΩ
• Continuity testing at 200 mA down to 0.01 Ω
• Live circuit warning (voltage display) and test inhibit
• Digital/analogue display

 

MEGGER MIT400/2 MIT410/2 MIT420/2 MIT430/2 CAT IV INSULATION TESTER WITH 1000V

• nsulation testing up to 1000 V and 200 GΩ range
• Stabilised insulation test voltage (New)
• Single range, faster continuity testing from 0.01 Ω to 1 MΩ (New)
• 600 V T RMS AC and DC voltage measurement

 

MEGGER SVERKER900 THREE PHASE RELAY TESTER

• The toolbox for substation 3-phase testing
• Three currents and four voltages
• Stand-alone functionality
• Rugged and reliable for field use
• Generation of 900 V and 105 A in single phase mode
• Secondary and primary testing

 

UNIVERSAL CIRCUIT BREAKER TEST SETS MEGGER PS-9130 AND PS-9160

• Proven power train
• Rugged instrumentation and controls
• Direct connection of draw-out type breakers
• Integral clock/calendar
• Easy-to-read display

 

AC VOLTAGE DETECTORS MEGGER - VF1 AND VF2

• Socket outlets
• Fuses
• Switches
• Wires and cables
• Circuit breakers
• Luminares

 

FREQUENCY RESPONSE ANALYZER MEGGER FRAX200 FRAX150 FOR POWER TRANSFORMER

• High dynamic range and accuracy
• Easy-to-use support software with advanced analysis tools
• Smallest SFRA instrument in the industry
• Hardware designed to ensure repeatable connections
• Fulfils international standards for SFRA

 

MEGGER DELTA4110 INSULATION POWER & DISSIPATION FACTOR TEST SET DELTA4000

• fully automatic 12 kV insulation power factor / dissipation factor (tan delta) test set
• Voltage: 25 V to 12 kV, 1 V resolution
• Current : 0 to 5 Amps, 0.1 µA maximum resolution
• Capacitance: 0 to 100 µF, 0.01 pF maximum resolution
• Inductance: 6 H to 10 MH, 0.1 mH maximum resolution
• Power factor PF : 0-100% (0-1), 0.001% maximum resolution
• Dissipation factor DF : 0-100 (0-10,000%), 0.001% maximum resolution
• Watt Loss: 0 to 2 kW
• Automatic and manual operation
• Accurate and repeatable measurement results with high noise suppression
• Lightweight, rugged two-piece design

 

MEGGER MIT300 MIT310 MIT320 MIT330 INSULATION AND CONTINUITY TESTER

• Extremely easy to use
• Tough rubber armoured case
• Self contained protective cover
• Live circuit warning
• Weatherproof to IP54

 

AUTOMATIC OIL CIRCUIT RECLOSER TESTER MEGGER OCR8015/9150

• Preprogrammed test sequences for reclosers and sectionalizers
• High-capacity outputs to test virtually all reclosers
• Accurate duplication of high-voltage test results
• Simple operation and precise test results
• Simplified adjustment of test current