Cod: Vanguard EZCT-2000C Plus
Descriere
The EZCT-2000C Plus is Vanguard’s third-generation microprocessor-based current transformer test set. Designed specifically for CT testing, the EZCT-2000C Plus has the following outstanding features that can greatly increase productivity and save time during the commissioning stage:
The EZCT-2000C Plus’ test leads can be connected to all the CT output terminals, and the complete CT test can be performed automatically without any operator intervention.
Excitation Test
The CT excitation test is performed using the
ANSI/IEEE C57.13.1 test method. Test voltage
ranges from 50, 300, 500,1200 and 2000 Vac
can be selected for the excitation test. The test
voltage is raised and lowered automatically by
the EZCT-2000C Plus. The excitation test voltage
and current data is collected and stored in
the unit's internal memory. Knee point voltages
(ANSI 10/50, IEC 60044, IEEE-30, IEEE-45) are
calculated and printed on the test report. All of
the test leads can be connected to the CT output
terminals (X1, X2, X3, X4 and X5), and there is
no lead switching required during testing. This
convenient arrangement allows for testing any
of the 10 possible combinations of X1 to X5. Up
to 10 excitation tests can be stored in one record.
Once the test is completed, the test report
and CT excitation curves can be printed on the
built-in thermal printer.
Demagnetization
The EZCT-2000C Plus automatically demagnetizes
the CT under test when performing an
excitation test.
Winding Resistance Test
The EZCT-2000C Plus can measure the DC
resistance of transformer windings from 100
micro-ohms to 10 ohms.
CT Winding Insulation
Resistance Test Feature
The EZCT-2000C Plus offers an IR test feature
that can also measure the insulation resistance
of the CT’s secondary winding using a test voltage
up to 1000 Vdc. The DC winding resistance
reading range is from 2 to 500 Mega-ohms. The
insulation resistance test results are displayed
and printed on the report.
Ratio and Polarity Tests
The CT current-ratio is determined using the
ANSI/IEEE C57.12.90 measurement method. A
test voltage is applied on any two terminals (X1
to X5) of the CT, and the induced voltage is measured
through the H1 and H2 terminals of the CT.
The CT current-ratio is displayed and also stored
in memory. The current-ratio is measured from
0.8 to 5,000. The CT winding polarity is displayed
as a "+" sign (in-phase) or a "-" sign (outof-
phase) and is annotated with the phase angle
in degrees. The CT current ratio error and phase
displacement is also calculated based on the CT
burden (or rated power) and rated current.
CT Burden Test
The EZCT-2000C Plus can measure the CT’s actual
connected burden by injecting a 1A or 5A
test current into the load. The CT burden measurements
(Voltage, current, Cos f, and burden
impedance) are displayed on the screen and
printed on the test report. This important test
verifi es the actual CT measured burden before
putting the CT in service, thus avoiding any potential
confi guration confl icts.
Accesorii standard
Alte produse VANGUARD
|
MICROOHMMETRU AUTOMATIC REZISTENTE DE CONTACT INTRERUPATOARE 200A VANGUARD AUTO-OHM 200 S3
• 1 to 200A programmable test current |
|
ANALIZOR COMUTATOR PLOTURI IN SARCINA SI REZISTENTA INFASURARE TRANSFORMATOR TRIFAZAT VANGUARD LTCA-40
• Auto discharge circuit for operator safety |
|
TRUSA INJECTIE CURENTI PRIMARI 600A AC TESTARE RELEE DE PROTECTIE VANGUARD PCI-600
• Results displayed on a 4-line by 20-character backlit LCD |
|
OHMMETRU REZISTENTA INFASURARI SI BOBINAJ TRANSFORMATOARE INDUCTIVE DE MARE PUTERE VANGUARD WRM-10P
• Range from 1 micro-ohm to 2,000 ohm |
|
TESTER AUTOMAT MASURA TRANSFORMARE TRANSFORMATOARE TRIFAZATE VANGUARD TRI-PHASE
• Generates its own 3-phase transformer test voltage from single-phase AC or DC Power input |
|
ANALIZOR INTRERUPATOARE TIMPI SI REZISTENTA DE CONTACT COMUTATOARE VANGUARD CT-8000
• dry-contact inputs 3 channels (9103-UC) or 6 channels (9104-UC) |
|
PUNTE TESTARE REZISTENTE INFASURARI TRANSFORMATOARE VANGUARD TRM-40
• accurately measure resistance values from 1 micro-ohm to 500 Ohms |
|
ANALIZOR CIRCUITE INTRERUPATOARE INALTA TENSIUNE VANGUARD DIGITMR PC
• dry-contact inputs 3 dry-contact channels |
|
SURSA DE PUTERE CURENT 10A AC/DC REGLABILA PENTRU TESTARE INTRERUPATOARE SI RELEE DE PROTECTIE VANGUARD UPS-S2
• Isolated variable 1-300 Vdc source |
|
TESTER RAPORT TRANSFORMARE TRANSFORMATOARE DE TENSIUNE CAPACITIVE VANGUARD CVT-765
• Standalone or computer-controlled |