125A max
250V
The MG 30-N is a rugged and powerful injection set which is especially
suited for testing over or under current or voltage relays. It is also suitable
for testing chneider Statimax type relays which are powered from the measurement
connection.
This instrument has one generator which serves both for current and
voltage, and a digital measurement and recording module with a large graphic
display. This enables measurement of the true RMS value of the current and
offers advanced timing and injection control functions.
OVERVIEW
- Flight Case enclosure
- Dim. L x H x P 260 x 290 x 270 mm
- Weight : 9 kg.
CARACTÉRISTICS
Power supply :
- 230V 50/60 Hz Pmax : 500VA.
Protections :
- Power supply and generator by circuit breakerson front face
Generator :
Single continuous variable generator in current or voltage
· 35A voltage max 5V(70A/2mn, 105A/40S, 120A/20s)
· 20A voltage max 12V(40A/30s, 60A/10s)
· 0.5A voltage max250V(1A/1mn, 2A/20s)
· 5A nominal power 7,5VA(10A/15s)
· 1A nominal power 1,3VA(1.8A/2mn)
All output can be overloaded like above
DIGITAL DISPLAY
The latest controler enables recording of trip time, threshold and CT ratio in an internal
FLASH memory. These data can be downloaded to a computer with windows® 9x/NT/XP/2000/
Seven. The data connexions are USB and RS232.
Ammeter :
- 2 rangess 0-12 A and 12-125 A with automatic selection
- Precision : 1%
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- free of voltage contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999