VE 1200-N Primary injection set
Single-phase test set for high currents. The easy to use and rugged VE 1200-N is particularly adapted to primary testing : transformer ratios, auxiliaries, bushings, circuit breakers, overcurrent relays, etc.
The VE1200-N has a built-in digital measurement and control module.
The latest version has a big graphical display for easy reading of the TRMS current and control of the injection.
OVERVIEW
- Flight Case with wheels,
- Size : 570 x 310 x 510 mm,
- Weight ± 52 kg.
SPECIFICATIONS
Power supply :
- 230 Vac 50/60 Hz.
Protection :
Supply and generator by circuit breakers and electronic control.
Generator :
Single generator configured for current three ranges : 1A, 15A and 2000A.
The output current can be adjusted to
650A for 15 minutes
1000A for 5 mn
2000A for 30 seconds.
DIGITAL DISPLAY
The new control enables recording of trip time, threshold and CT ratio in an internal
FLASH memory. These data can be downloaded to a computer with windows® XP/2000/VISTA.
The data connexions are USB and RS232.
Internal ammeter :
- 2 ranges 0-200 A and 200-2000 A with automatic selection
- Precision : 1%.
External ammeter :
- 2 ranges 0-1A and 1-10A
- Precision : 0.5 %
- The external ammeter has a dedicated menu for measuring the ratio and phase shift of a Current Transformer.
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- free of voltage contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999 s