Vacuum Bottle Tester for High Voltage Circuit Breaker test Vanguard VBT-60

Code: Vanguard VBT-60 / VBT-80


 

Datasheet PDF, 0.42 Mb
   

Description

  • Automatic Testing
  • 10 kV to 60 kV DC output in 5 kV steps
  • Selectable dwell time from 5 seconds to 2 minutes
  • Digital voltage and current display
  • Failure indicator lamp
  • Very light-weight

 

VBT-60/VBT-80

vacuum bottle testers

The VBT-60 and VBT-80 are microprocessor-based, portable, dc (60 kV and 80

kV, respectively) vacuum bottle testers. These lightweight, portable testers are

designed for testing circuit-breaker vacuum bottles in the fi eld and at the shop.

Test voltages can be selected from 10 kV dc to 60 kV dc in 5 kV steps for the

VBT-60 and from 10 kV to 80 kV dc in 5 kV steps for the VBT-80. The high-voltage

test time can be set from 5 seconds to 2 minutes. The test voltage is raised

to the selected voltage and held for the test time duration. After the test time

duration has elapsed and the leakage current did not pass the preset value of

100 µA, 200 µA, or 300 µA, the test voltage is returned to zero. If a fl ash-over

condition occurs, such as bottle failure, the test voltage is immediately turned

off, a "Failure" message is displayed on the LCD screen, and the "TEST FAIL" LED

light on the unit is also illuminated.

The presence of high voltage is indicated by an audible tone and an illuminated

"HIGH VOLTAGE" LED light. For additional operator safety, an "ARM" switch

must be held down during testing.

The VBT-60 and VBT-80 feature a back-lit LCD screen (16 characters by 2 lines)

that is viewable in both bright sunlight and low-light levels. A turn-and-press

knob is used to control the unit. An RS-232C interface port is provided for factory

calibration and diagnostic testing.

Each unit is furnished with a 10-foot test cable that is terminated with a quickdisconnect

test clip. A transportation case is also included.

 

Standard accessories

Part number VBT-60 VBT-60 and cables

Part number VBT-80 VBT-80 and cables

Part number VBT-HV-CABLE Hight Voltage Cable

 

More products VANGUARD

CAPACITIVE VOLTAGE TRANSFORMER TURN RATIO TESTER VANGUARD CVT-765

• Standalone or computer-controlled
• Can test CVT's rated up to 765 KV
• Displays turns-ratios from 75-15,000
• Calculates turns-ratio percentage error when nameplate voltages are provided

 

LOAD TAP CHANGER ANALYZER AND WINDING RESISTANCE ANALYZER VANGUARD LTCA-10

• Auto discharge circuit for operator safety
• 3 resistance reading channels including one dynamic channel
• Digital resistance reading from 1 micro-ohm to 500 ohms
• Calculate equivalent resistance value at reference temperature
• Stores 50 static records and 20 dynamic records
• Built-in 4.5-inch thermal printer
• Weighs less than 44 lbs.

 

THREE-PHASE TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance from 1 micro-ohm to 500 Ohms
• Perform three phase test on a transformer without the need to switch cables
• Can provide individual Delta winding resistance values
• Can provide individual Wye (with no neutral) winding resistance values
• Demagnetize transformer after test
• Selectable test current from 1A to 40A
• Computer control via RS-232C, USB, or Bluetooth interface
• Built-in 2.5" wide thermal printer

 

TRANSOFORMER BREAKER CONTACT RESISTANCE MICRO OHM METER 600A VANGUARD DMOM-600

• 10 to 600A programmable test current
• Resitance range: 1.5m? at 600A to 450m? at 10A
• Measures circuit breaker contact resistance with safety ground on (with the Dual Ground option)
• Stores test records on-board or on external USB Flash drive
• Built-in 2.5" wide thermal printer

 

TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance values from 1 micro-ohm to 2,000 Ohms
• Auto-discharge circuit for operator safety
• Demagnetizes transformer after test
• Selectable test current from 1A to 20A
• RS-232C, USB, and Bluetooth computer interfaces
• Built-in thermal printer

 

EHV HIGH VOLTAGE CIRCUIT BREAKER ANALYZER VANGUARD DIGITMR PC

• dry-contact inputs 3 dry-contact channels
• timing windows 1 second, 10 seconds, or 20 seconds
• timing resolutions ±50 micro-seconds @ 1 sec. duration
• Inexpensive, PC-controlled EHV circuit breaker analyzer
• Optional "on-line" timing mode
• Small and light-weight
• Can test contact time, stroke, velocity, over-travel, and contact wipe

 

WINDING RESISTANCE OHMMETER FOR TESTING HIGH POWER INDUCTIVE TRANSFORMERS VANGUARD WRM-10P

• Range from 1 micro-ohm to 2,000 ohm
• Up to 10 Amperes of test current
• Auto discharge circuit for operator safety
• Built-in 2.5" Thermal Printer, computer interface
• Stores 48 records of 63 readings
• Weighs less than 27 lbs.

 

DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-7000

• dry-contact inputs: 3 channels (9021-UC) or 6 channels (9100-UC)
• timing windows: 1 second, 10 seconds, or 20 seconds
• timing resolutions ±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration
• breaker operations: Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
• Fully analyze circuit breaker's performance
• measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
• USB computer interface
• USB Flash drive interface (Flash drive not included)
• Built-in 4.5" wide Thermal Printer

 

ON-LOAD TAP CHANGER ANALYZER AND WINDING RESISTANCE ANALYZER ON 3-PHASE TRANSFORMERS VANGUARD LTCA-40

• Auto discharge circuit for operator safety
• 3 resistance reading channels including one dynamic channel
• Digital resistance reading from 1 micro-ohm to 500 ohms
• 60Vdc power supply , outputting 40 amperes
• Calculate equivalent resistance value at reference temperature
• Stores 50 static records and 20 dynamic records
• Built-in 4.5-inch thermal printer

 

CURRENT TRANSFORMER TEST SET TURN RATIO, EXCITATION, SATURATION, POLARITY VANGUARD EZCT-2000A

• Perform Saturation, Ratio and Polarity Tests
• Perform CT Winding Resistance Test
• Fully Automated
• Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments
• Plot Multiple Saturation Curves
• Store 140 Records (of 10 Saturation Curves)
• Computer Interface
• USB Flash drive interface