Vacuum Bottle Tester for High Voltage Circuit Breaker test Vanguard VBT-60

Code: Vanguard VBT-60 / VBT-80


 

Datasheet PDF, 0.42 Mb
   

Description

  • Automatic Testing
  • 10 kV to 60 kV DC output in 5 kV steps
  • Selectable dwell time from 5 seconds to 2 minutes
  • Digital voltage and current display
  • Failure indicator lamp
  • Very light-weight

 

VBT-60/VBT-80

vacuum bottle testers

The VBT-60 and VBT-80 are microprocessor-based, portable, dc (60 kV and 80

kV, respectively) vacuum bottle testers. These lightweight, portable testers are

designed for testing circuit-breaker vacuum bottles in the fi eld and at the shop.

Test voltages can be selected from 10 kV dc to 60 kV dc in 5 kV steps for the

VBT-60 and from 10 kV to 80 kV dc in 5 kV steps for the VBT-80. The high-voltage

test time can be set from 5 seconds to 2 minutes. The test voltage is raised

to the selected voltage and held for the test time duration. After the test time

duration has elapsed and the leakage current did not pass the preset value of

100 µA, 200 µA, or 300 µA, the test voltage is returned to zero. If a fl ash-over

condition occurs, such as bottle failure, the test voltage is immediately turned

off, a "Failure" message is displayed on the LCD screen, and the "TEST FAIL" LED

light on the unit is also illuminated.

The presence of high voltage is indicated by an audible tone and an illuminated

"HIGH VOLTAGE" LED light. For additional operator safety, an "ARM" switch

must be held down during testing.

The VBT-60 and VBT-80 feature a back-lit LCD screen (16 characters by 2 lines)

that is viewable in both bright sunlight and low-light levels. A turn-and-press

knob is used to control the unit. An RS-232C interface port is provided for factory

calibration and diagnostic testing.

Each unit is furnished with a 10-foot test cable that is terminated with a quickdisconnect

test clip. A transportation case is also included.

 

Standard accessories

Part number VBT-60 VBT-60 and cables

Part number VBT-80 VBT-80 and cables

Part number VBT-HV-CABLE Hight Voltage Cable

 

More products VANGUARD

THREE-PHASE TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance from 1 micro-ohm to 500 Ohms
• Perform three phase test on a transformer without the need to switch cables
• Can provide individual Delta winding resistance values
• Can provide individual Wye (with no neutral) winding resistance values
• Demagnetize transformer after test
• Selectable test current from 1A to 40A
• Computer control via RS-232C, USB, or Bluetooth interface
• Built-in 2.5" wide thermal printer

 

600A AC PRIMARY CURRENT INJECTION SOURCE FOR RELAY TESTING VANGUARD PCI-600

• Results displayed on a 4-line by 20-character backlit LCD
• Test currents from 10 to 600 amperes AC
• Also has an external-current input (0-10 A)
• timer reading range 1 m.. 2 hours

 

DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-3500

• Dry-contact inputs: 3 channels
• Trigger input voltage open/close: 30 ¬ 300 V, DC or peak AC
• Breaker operations: Open, Close, Open-Close, Close-Open
• Timing resolution: ±0.1 millisecond
• Detect Main & Insertion Resistor Contacts on same input
• USB computer interface
• Built-in 2.5" wide Thermal Printer

 

TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-01

• Displays turns-ratio from 0.8-15,000
• Calculates turns-ratio percentage error
• Displays winding polarity and phase angle
• Displays excitation current
• Battery or AC-powered (ATRT-01B S3 only)
• Standalone or computer-controlled

 

THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03

• Highest ratio: 0.8 - 15,000
• Built-in 4.5" thermal printer
• Excitation current measuring
• Phase angle measuring
• Computer interface
• Name-plate turns ratio calculation
• Computed % error based on measured and calculated ratio

 

AUTOMATIC THREE-PHASE TRANSFORMER TURN RATIO METER VANGUARD ATRT-03A

• Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC, and Australian standards plus phase shifting transformers
• Store up to 128 transformer test-plans in Flash EEPROM
• Store up to 112 test records in Flash EEPROM
• Built-in USB Flash Drive Interface
• Computer Interface (RS-232C and USB Port)
• 4.5 Inch thermal printer
• Built-in transformer load tap changer

 

THREE-PHASE TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance from 1 micro-ohm to 2000 Ohms
• Perform three phase test on a transformer without the need to switch cables
• Can provide individual Delta winding resistance values
• Can provide individual Wye (with no neutral) winding resistance values
• Demagnetize transformer after test
• Selectable test current from 1A to 20A
• Computer control via RS-232C, USB, or Bluetooth interface
• Built-in 2.5" wide thermal printer

 

EHV HIGH VOLTAGE CIRCUIT BREAKER ANALYZER VANGUARD DIGITMR

• dry-contact inputs 3 dry-contact channels
• timing windows 1 second, 10 seconds, or 20 seconds
• timing resolutions ±50 micro-seconds @ 1 sec. duration
• Stand-alone, microcomputer-driven EHV Circuit Breaker Analyzer
• Analyzes contact time, stroke, velocity, over-travel, and contact wipe
• USB PC interface & USB Flash drive interface
• Built-in thermal printer

 

VACUUM BOTTLE TESTER FOR HIGH VOLTAGE CIRCUIT BREAKER TEST VANGUARD VBT-60

• Automatic Testing
• 10 kV to 60 / 80 kV DC output in 5 kV steps
• Selectable dwell time from 5 seconds to 2 minutes
• Digital voltage and current display
• Failure indicator lamp
• Very light-weight

 

TRANSFORMER WINDING RESISTANCE TESTER VANGUARD TRM-40

• accurately measure resistance values from 1 micro-ohm to 500 Ohms
• Auto-discharge circuit for operator safety
• Demagnetizes transformer after test
• Selectable test current from 1A to 40A
• RS-232C, USB, and Bluetooth computer interfaces
• Built-in thermal printer