Transformer On-Load Tap Changer Tester Testyle TE2060 oltc switch turn ratio

    office@distek.ro     ROM     ENG  
Login | Create account | Forgot password?
Product cart  Products: 0 | Total: 0    
 
 
    Home |  About Us |  News |  Promotions |  Discounts |  Services |  Tech Library |  How to order? |  Sitemap |  Contact
 
 
Products         [+ Expand]   [- Colapse]

Transformers Test > TESTYLE (26) > Transformer On-Load Tap Changer Tester Testyle TE2060

 


  ..  Products navigator [15] from [26]    ..
 

Transformer On-Load Tap Changer Tester Testyle TE2060

Code: Testyle TE2060
 
Testyle
 
 Product Datasheet (*.PDF - 0.15 Mb)

» Technical Specs

It is an integrated instrument used for measurement and analysis power transformers and special transformers on-load tap changer’s electrical performance of power system. It adopts computer-controlled, through a specially designed measuring circuit can be realized measurement of on-load tap changer’s transition time, transition waveform, the transition resistance, three-phase simultaneous performance and other parameters. According to the user’s needs and field conditions, it not only can directly lead measure from tap changer, but also can use the transformer three-phase bushing and the neutral point lead measure directly.In accordance with IEC standards IEC 61010-1. Safety requirements for electrical equipments  used in measurement, control and laboratory.

 

(1) Light oscillograph function
(2) Strong comprehensive measurement capability
(3) Comprehensive analysis of test results
(4) Data hold, data communication
(5) Strong anti-interference
(6) Large-screen LCD display, Chinese menu operation
(7) Own micro-printer, Chinese-characterizing print measurement result and waveform 
(8) Small size, light weight

 

 

Power supply

10% Power≤200W±  220V

Executive Standard

  IEC 61010-1. Safety requirements for electrical equipments used in measurement, control and laboratory.

 Dimensions

  410mm×320mm×200mm

 Weight

  ≤20kg

 Monitor

  240*128Wide temperature range type LCD

 Printer

  MP-40-8 panel type front changing paper printer

 Processing part

  80C320 high-speed 8-bit microprocessor. Program memory 32K; power down to keep the data memory 512K bytes; high-speed A / D converter, the maximum sampling rate up to 400KHZ
 

 Transition resistance measurement range

W  Y type transformer 1-40A

W  Y type transformer 1-20A

 Measurement Accuracy

  1-5A ,Δ≤±10%

  5-40A , Δ≤±5%

 Time error

  Δ≤±1%

 

Home |  About Us |  News |  Promotions |  Discounts |  Services |  Tech Library |  Terms and Conditions |  How to order? |  Useful links |  Sitemap |  Contact |  Politica Cookie

        
Copyright © 2010 - 2024 / Distek