TE5812 Microprocessor-based Protective Relay Tester can output high-precision six-phase AC/DC voltage, current source, applicable to any microprocessor relay protection testing; uses Windows XP user interface, large color display directly, touch mouse, makes test easier.In accordance with IEC standards IEC 60255-11 2008(Ed.2.0) Measuring relays and protection equipment–Part 11.
(1)Six-phase current, six-phase voltage simultaneous output.
(2) Control board, with DSP + FPGA structure, 16-bit DAC output, can produce 2000 high-density sine wave on the fundamental points of every cycle. As a domestic tester, it represents the highest level, greatly improved waveform quality and increase the accuracy.
(3) Standalone operation, built-in high-performance industrial computer, dominant frequency 300 ~ 600MHZ, 128M memory, 12G hard disk drive, running Windows XP operating system, panel with advanced stainless steel keyboard and touch mouse, 8.4 inches TFT true color LCD.
(4) This device can test a variety of relay protection and automatic safety devices, and can simulate complex transient, permanent, transitional fault for the full group equipment tests, also can save real time test data, display vector graph, drawing all kinds of curves and online print reports.
Power supply |
AC220V±10%; 50Hz 10A |
Executive Standard |
IEC 60255-11_2008(Ed.2.0) Measuring relays and protection equipment–Part 11 |
AC Current Source |
Amplitude range: 6×(0-30A)Accuracy: 0.2% |
Maximum six-phase current parallel output: 180A |
Permit value for long-term work of phase current: 10A |
Power: 300VA/phase |
Maximum power for six-phase parallel:900VA |
Maximum allowed working hours for Six-phase parallel output:10s |
Frequency range: 0--1000Hz;Accuracy: 0.001Hz |
Harmonic times: 2—20 orders ; Phase: 0--360° ;Accuracy: 0.1° |
DC Voltage Source |
Phase voltage output amplitude: 0--±150V ;Accuracy: 0.2% |
Line voltage output amplitude: 0--±300V |
Time Measurement Range |
Range: 1ms~9999s |
Measurement accuracy: 1ms |
DC Current Source |
Amplitude: 30A/phase |
Power: 300VA/phase |
Accuracy: 0.2% |
AC Voltage Source |
Amplitude range: 6 ×(0--125V) ; Accuracy: 0.2% |
Line voltage range: 0--250V |
Phase voltage /line voltage output power: 75VA/100VA |
Frequency range: 0--1000Hz ;Accuracy: 0.001Hz |
Harmonic times:2—20 times |