Code: Megger TM1710 TM1720 TM1740 TM1750 TM1760
Description
• Provides reliable and accurate test results in noisy high voltage substations
• Four standard models. Full stand-alone functionality or data acquisition models without user interface.
• Fast and safer with DualGround™ testing, both sides of breaker grounded
• On-screen assistance with connection diagrams and test template Wizard
• All models can be controlled via computer
The TM1700 series circuit breaker analysers utilizes some of the ground breaking technology from the top of the line version TM1800. There are four models starting from PC-remote controlled to fully stand-alone. All models can be controlled from a computer using the well proven data management and analysing software CABA Win.
The robust design offers powerful technology that assists the user to achieve efficient and reliable circuit breaker testing. All inputs and outputs on the instrument are designed to withstand the challenging environment in high-voltage substations and industrial environments. Galvanically isolated inputs and outputs makes it possible to perform all relevant measurements in one test, eliminating the need for new setup and re-connections.
The patented DualGround™ method makes the testing safe and
time saving by keeping the circuit breaker grounded on both sides throughout the test.
The timing measurement inputs are using a patented Active Interference Suppression algorithm to ensure correct timing and accurate PIR (Pre-Insertion Resistor) values even at high capacitively coupled interference currents. The adaptive and easy-to-use software allow the user to perform the test by simply turning the test switch without the need for settings. The operator is only one click away from advanced help functions such as connection diagrams. The 8" color touch screen, with on-screen keyboard, allows the user to efficiently operate this high-level interface.
Standard accessories
Including:
?? Control 3 ch. (Auxiliary 3 ch.)
?? Timing M/R 6 ch.
?? Digital 6 ch.
?? CABA Win
Optional:
?? Analog 3 ch., DCM 6 ch.
With Analog option incl. analog cables BL-49092
TM1720 BL-49094
Including:
?? Control 6 ch. (Auxiliary 6 ch.)
?? Auxiliary 6 ch.
?? Timing M/R 6 ch.
?? Digital 6 ch.
?? CABA Win
Optional:
?? Analog 3 ch., DCM 6 ch.
With Analog option incl. analog cables BL-49096
TM1740 BL-49190
Including:
?? Control 3 ch. (Auxiliary 3 ch.)
?? Timing M/R 6 ch.
?? Digital 6 ch.
?? CABA Win
Optional:
?? Analog 3 ch., DCM 6 ch.
With Analog option incl. analog cables BL-49192
TM1750 BL-59090
Including:
?? Control 6 ch. (Auxiliary 6 ch.)
?? Auxiliary 6 ch.
?? Timing M/R 6 ch.
?? Digital 6 ch.
?? CABA Win
TM1760 BL-59094
Including:
?? Control 6 ch. (Auxiliary 6 ch.)
?? Auxiliary 6 ch.
?? Timing M/R 6 ch.
?? Digital 6 ch.
?? Analog 3
?? CABA Win
Optional:
?? Analog 3 ch., DCM 6 ch.
With Analog option incl. analog cables BL-59096
Included accessories, all models
Recommended options
Optional accessories
DCM1700 3 ch
Kit for 3-channels DualGround™ Timing BL-59190
DCM1700 6 ch
Kit for 6-channels DualGround™ Timing BL-59192
Keyboard HC-01090
Flight Case TM1700-series GD-00025
Digital Linear Transducer
TP1 300 XB-39140
TP1 500 XB-39150
Circuit breaker transducer kits
AHMA 4/8 (ABB) XB-61030
HMB 4/8 (ABB) XB-61040
First trip kits
For single operating mechanism BL-90700
For three operating mechanisms BL-90710
LTC135 Load Tap Changer power supply CG-92100
More products MEGGER
|
MICRO-OHMMETER MEGGER - MOM200A
• Easy to operate
|
|
MEGGER DLRO10X RESISTANCE OHMMETER DLRO 10 DLRO 10X 6111-428 6111-429
• up to 10A current |
|
MEGGER TORKEL-840 TORKEL-860 BS-49094 BS-49096 TELECOM BATTERY LOAD DISCHARGE TESTER FOR UPS CELLS
• used for battery systems ranging from 12 to 250 V |
|
MEGGER TORKEL 820 BS-49092 TELECOM BATTERY LOAD DISCHARGE TESTER PROGRAMMA
• Combines efficiency with portability |
|
PHOTOVOLTAIC KIT MEGGER - PVK320
• PVM210 irradiance meter
|
|
MEGGER BITE3 BATTERY IMPEDANCE TESTER
• Determines health of lead-acid cells up to 2000 Ah |
|
MEGGER TDR2000/2 TDR CABLE REFLECTOMETER FAULT LOCATOR TDR2000/2RM TDR2000/2R
• 20 km range at VF = 0.90 |
|
UNIVERSAL CIRCUIT BREAKER TEST SETS MEGGER DDA-3000 AND DDA-6000
• Model DDA-1 Digital Data Acquisition Instrumentation and Control System
|
|
MEGGER MPRT2145 SINGLE PHASE RELAY TESTER
• Open communication architecture for third party software application |
|
CIRCUIT BREAKER TEST SET MEGGER ½ CB-845
• Digital memory ammeter
|