High range 5 year life sensor - ideal for biomass appliances
Features
Independently tested by TÜV SUD to : EN50379 Use for : BS7967
Applications
Measures
Calculates
Fuels Types
Box Contents
Specification
May be subject to change
Parameter
Range
Resolution
Accuracy
Temp Measurement
Flue Temperature
0-600°C
0.1°C
±2.0°C±0.3% reading
Inlet TemperatureInternal Sensor
0-50°C
Inlet TemperatureExternal Sensor
Flue Gas Measurement
Oxygen*2
0-21%
0.1%
±0.3%
Carbon Monoxide*1
0-20ppm21-4,000ppm nom4,001-10,000ppm20,000ppm max for 15 mins
1ppm
±3ppm±5% of reading±10% of reading
Carbon Dioxide*1
0-20%
±0.3% volume
Efficiency (Net or Gross)*2
0-99.9%
±1.0% of reading
Efficiency High (C)*2
0-119.9%
Excess Air*2
0-250%
±0.2% of reading
CO/CO2 ratio*2
0-0.999
0.0001
±5% of reading
** Pressure (differential)
Nominal range ±1600mbar
±1mbar
Maximum 0.001mbar
±0.05mbar
Maximum over range without damage to sensor is ±800mbar
±160mbar
< 25mbar
±3% of reading
Pre-programmed Fuels
Natural gasPropaneButaneLPGLight Oils (28/35 sec)Wood Pellets plus 3 User Fuels
Storage Capacity
99 Combustion tests20 Pressure tests20 Tightness tests20 Temperature tests20 Room CO tests
*1Using dry gases at STP*2Calculated
Ambient Operating Range
0°C to ±45°C - 10% to 90% RH non-condensing
Battery Type / Life
4 AA cells - > 8 hours using Alkaline AA cells
Chargers (optional)
220v charger, for NiMH batteries only
Dimensions
Weight:
0.8kg handset with protective cover
Handset:
200 x 45 x 90mm
Probe
300mm long including handle.6mm diameter x 240mm long stainless steel shaft with 3m long neoprene hose.Type K thermocouple