PVCHECKs-PRO Commissioning tester for PV system up to 1500V / 40A

Code: PVCHECKs-PRO HV00PVPR


 

Datasheet PDF, 1.25 Mb
   

Description

PVCHECKs-PRO
Commissioning tester for PV system up to 1500V / 40A

PVCHECKs-PRO

Multifunction commissioning tester up to 1500V / 40A capable of taking the following measurements:
• Insulation measurement on PV modules/strings/fields up to 1500VDC (with PI and DAR calculation)
• Open circuit voltage Voc up to 1500V in accordance with IEC/EN62446
• Short circuit current Isc up to 40A in accordance with IEC/EN62446
• Continuity of protective conductors with 200mA
• Polarity
• GFL function for fault finding on strings and PV modules
• Tests on single-facial and bi-facial modules
• Automatic acquisition of the cell calibration value (by using suitable cells)
• OPT function for insulation testing on MLPE-equipped PV strings (including optimizers and RSDs), allowing measurements to be performed without the need to disconnect the MLPE devices*
*Soon available with the new update.
 

PVCHECKs-PRO is a commissioning tester designed to take all safety measurements and verifications of PV installations in accordance with IEC/EN62446. By a single GO-key stroke PVCHECKs-PRO performs all commissioning tests. Thanks to the seamless mode, PVCHECKs-PRO is able to test in sequence all strings of a combiner box by a single GO-key stroke. Finally, the GFL - Ground Fault Locator detects the precise position of the lack of insulation, speeding the troubleshooting.

Functions
Continuity of protective conductors with 200mA 
Polarity 
Open circuit voltage Voc of PV modules and strings1500V
Short circuit current Isc on PV modules and strings40A
PV string/field insulation with test voltage 250, 500, 1000, 1500VDC 
Use of SOLAR-03 remote unit with Bluetooth connection 
Measurement of direct (front side) irradiation with reference cellwith SOLAR03 remote unit (optional accessory)
Temperature measurement of cell and environmentwith SOLAR03 remote unit (optional accessory)
Measurement of polarization index P.I. 
Dielectric absorption ratio D.A.R 
OPT function for insulation testing on PV strings in the presence of MLPE devices such as optimizers and RSDs, without the need to disconnect them from the modulesComing soon with the new update
GFL function to locate the fault position in the string 
Measurement categoryCAT III 1000V AC, CAT III 1500VDC
Backlit LCD display 
Internal memory999 Locations
Integrated WiFi connection and compatibility with HTANALYSIS App 
Optical/USB serial port for PC connection 
Custom management of internal PV module database 
Auto power off 
Help on line on the display 
Size (LxWx H) (mm)235x165x75
Weight in grams (batteries included)1200
 

Standard accessories

STANDARD ACCESSORIES
KIT3PRO15 Set of 2 cables banana + 2 integrated alligator clips Blue/Green
KITPCMC415 Set of 2 cables MC4/banana + 2 adapters MC4/alligator clips, 3m, Red/Black
SP-5100 Set of straps for shoulder instrument use
C2006 Optics/USB connection cable
YABAT0003000 Rechargeable battery type AA NiMH, 1.2V (6 pc)
YABAT0004001 External battery charger
VA507 Rigid carrying case
Quick start guide
Calibration report
Complete user manual and management software available online
 

Recommended options

OPTIONAL ACCESSORIES
PT305 Temperature probe PT1000
HT305 Photovoltaic cell to measure solar radiation (with fixing bracket)
M304 Mechanical inclinometer to detect the correct solar incidence angle
SOLAR03 Remote unit with 1 temperature input and 3 irradiation inputs (for HT305) complete
with magnetic belt
KITPVPROEXT20 2 extension cables banana pin - banana jack 20m (red and black)
SP-2002 Strap with magnetic attachment for SOLAR03
KIT2TIPS15 Set of 2 Black/Red leads with MC4 termination
 

More products HT ITALIA

HANDHELD DIGITAL MEGOHMMETER INSULATION & CONTINUITY 4 GOHM 1000V HT ITALIA M70

• Insulation with test voltage 250, 500, 1000VDC
• Up to 4Gohm measurement range
• Automatic discharge of device under test
• LOCK feature for continuous measurements
• Programmable timer up to 60s
• Continuity of earth conductors with test current of 200mA
• A/DC voltage up to 600V
• Resistance and continuity test with buzzer

 

HT2055 STEP AND CONTACT METER UP TO 50A

• TRMS
• Measuring range 200Ω
• Earth resistance by 2- and 3-wire method
• Ground resistivity by 4-wire method
• Compensation of disturbance voltages
• Compensation of test cables
• Measurement of step/contact voltage

 

MULTIFUNCTION PORTABLE MULTIMETER FOR EARTH RESISTANCE MEASUREMENT HT ITALIA M73

• Trip out time measure on AC Standard RCD's
• Trip out current: 30, 30x5, 100, 300mA
• Global Earth Resistance with 0.1Ohm resolution
• Global Earth Resistance without RCD's tripping
• DC Voltage
• AC TRMS Voltage
• Automatic detection of AC/DC signals

 

HT SOLAR I-VE MULTIFUNCTION I-V CURVE TRACER FOR PHOTOVOLTAIC SYSTEMS

• 1500V Multifunction I-V Curve Tracer for maintenance and efficiency tests on single-phase installations.
• Measurement of efficiency of a single-phase photovoltaic system
• Measurement of I-V Curve of a module or of a string up to 1500V/10A - 1000V/15A
• Measurement of open-circuit voltage of a module or of a string (VOC) 1500V
• Measurement of short-circuit current of a module or of a string (ISC) 15A

 

POWER ANALYZER CURRENT CLAMP METER HT ITALIA HT9022

• DC, AC + DC TRMS current up to 1000A
• DC, AC + DC TRMS voltage up to 1000V
• Resistance and continuity test
• Active, Reactive, Apparent power on Single/Three phase systems
• Active, Reactive energy on Single/Three phase systems
• Power Factor on Single/Three phase systems
• Harmonic voltage/current up to 25th with THD% calculation
• PC connection via Bluetooth

 

HT8100 PROFESSIONAL PROCESS CALIBRATOR WITH MULTIMETER FUNCTIONS

• TRMS
• AC/DC voltage 1000V AC+DC
• AC/DC current 1A AC+DC
• DC 4-20mA current measurement
• DC 0-10V voltage measurement
• DC 4-20mA current generation

 

HT GSC60 MULTIFUNCTION ELECTRICAL INSTALLATION TESTER WITH POWER QUALITY ANALYSIS

• Insulation with voltage 50, 100, 250, 500, 1000VDC
• Three-phase Power quality and Energy consumption analysis
• 632 parameters can be recorded for over two months
• Voltage/current vector diagram
• Voltage/current waveforms
• Tables or histograms of Harmonics and THD%
• Integrated WiFi connection and compatibility with HTANALYSIS App

 

SINGLE/ THREE-PHASE NETWORK AC VOLTAGE DATA LOGGER HT ITALIA XL423/ XL424

• TRMS AC Voltage measure up to 600V
• Recording with sampling programmable period
• Manual activation of recording
• RS-232 interface
• Programming with DATALINK software

 

EARTH RESISTANCE AND LOOP IMPEDANCE RCD TESTER HT ITALIA SPEED 418

• Tripping time on RCD type A, AC General and Selective with currents 10, 30,100, 300, 500mA
• Tripping time on RCD type AC General with currents 30, 30x5, 100, 300mA
• Tripping current on RCD type A, AC General and Selective Global earth resistance without RCD tripping
• Line/Loop impedance, also with high-resolution (0.1m )( with optional accessory IMP57)
• Optical/USB interface for connection to PC

 

INFRARED NON CONTACT THERMOMETER HT ITALIA

• Infrared temperature measurement from -50°C to 1000 °C
• Emissivity regulation
• Distance / Spot ratio of 50:1
• Laser pointer activation