Generates its own 3-phase transformer test voltage from single-phase AC or DC Power input
-
Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC, and Australian standards plus phase shifting transformers
-
64 x 128 graphic LCD screen
-
Store up to 128 transformer test-plans in Flash EEPROM
-
Store up to 112 test records in Flash EEPROM
-
Built-in USB Flash Drive Interface
-
Computer Interface (RS-232C and USB Port)
-
4.5 Inch thermal printer
-
Built-in transformer load tap changer
-
Powered from a single phase 100-264 Vac 50/60 H
Vanguard’s new TRI-PHASE is a true 3-phase transformer turns ratio tester designed to conform to the IEEE C57.12.90 measurement method. The TRI-PHASE outputs a 3-phase excitation test voltage to the three transformer primary windings. The induced 3-phase secondary voltages are sensed and the transformer turns ratio is calculated. The TRI-PHASE is capable of measuring turns ratios from 0.8 to 15,000. The 3-phase excitation current, phase angle readings along with the turns ratios are displayed on the built-in LCD. Since a 3-phase voltage is used to excite the transformer windings, the TRI-PHASE can detect and measure turns ratios of any transformer type. The TRI-PHASETM can easily measure the turns ratio of phase-shifting transformers where other 3-phase transformer ratio testers cannot.
Transformer Test Voltages
The Tri-Phase generates three-phase transformer
test voltages from a single-phase AC or
DC power source. Three test voltages (8 Vac, 40
Vac, 100 Vac) allow the Tri-Phase to test CT’s
and PT’s, as well as power transformers.
Auto-Detect Transformer
Confi guration
The Tri-Phase can automatically detect 130 different
transformer types defi ned by ANSI, CEI/
IEC, and Australian standards, as well as phaseshifting
transformers.
Internal Test Record
Storage
Up to 112 test records can be stored in the Tri-
Phases’s Flash EEPROM. Each test record may
contain up to 99 turns-ratio, excitation current,
phase angle, and nameplate voltage readings.
Test records can be recalled locally or transferred
to a PC via the available interfaces (RS-
232C port, USB port, USB Flash drive port).
Transformer Test Plans
The Tri-Phase can store up to 128 transformer
test-plans in its Flash EEPROM. A test-plan
is comprised of the transformer nameplate
voltages for each tap setting. The calculated
turns-ratio based on the nameplate voltages is
compared with the measured turns-ratio to derive
the percentage error and Pass/Fail results.
By recalling a test plan, a transformer can be
quickly tested and turns-ratio Pass/Fail reports
can be reviewed. Test plans can be created with
the PC software and can be transferred to the
Tri-Phase via the available interfaces (RS-232C
port, USB port, USB Flash drive port).