Portable AC/DC neon indicator with domed contact electrode for use on systems up to 33kV
AC/DC neon indicators
UK Electricity Council Approval list G12
KD1E/33
The KD1E/33 is a neon HV potential indicator suitable for use on earthed neutral systems up to 33kV. A range of highly portable, neon and digital potential indicators, these instruments provide a means of confirming the presence of voltage on earthed neutral electrical circuits.
Conforming in design lengths to recommended creepage and safety standards, the KDIE series features high grade PVC tubing and incorporates totally encapsulated resistor chains. For additional safety a proving unit (PH3) is available and should be used before and after the high voltage indicator is employed.
KD1E/33
Technical specification
Maximum System voltage
33kV
Maximum Voltage to earth
19kV
Threshold voltage
300V
Measuring Range
N/A
Resolution
N/A
Sensitivity
AC/DC
Circuit current (IEC 61234-2)
1.1mA nominal @19kV
Dielectric leakage current (IEC 61234-2)
17uA nominal @ 40kV
Length (mm)
670
Diameter (mm)
25
Handle length (mm)
250
Hand guard height (mm)
Contact Electrode Type
» Accesorii standard incluse
Models:
Neon Indication
KD1E 1KV - 11.5KV 113A916
KD1E/KAD 1KV - 11.5KV KAD Audio Alarm 113A915
KD1E/19 1.5KV - 19KV 113A914
KD1E/19S 1.5KV - 19KV AC Voltage only 113A913
KD1E/22 3KV - 22KV 113A912
KD1E/33 3KV - 33KV 113A911
Digital Readout
KD1E/15D 15KVmax Resolution-10V 109A910
KD1E/33D33KVmax Resolution-100V 109A911
» Optiuni, Servicii si Accesorii recomandate
ACCESSORIES
PH3 112A913 (domed)
112A921 (flat nose)
Proving unit for proof testing high voltage indicators
High voltage output 1200V -1500DC
Self test facility
Avoids use of known supply points or bulky test equipment
Bent End Adaptors90° or 120°
141A900 – 90°
141A912 – 120°
Suitable for use on vertical type switchgear
Extension Rod 141A901
1.5m extension rod for use on overhead lines
Suitable for use with KDIE/15D, KDIE/33D, PR15D and PR33D