Description
The Vanguard MCCB-250 is a programmable, high-current source designed specifically for testing molded-case circuit breakers, thermal magnetic and solid-state overload motor-protection relays.
Built-in Timer
The MCCB-250’s built-in timer can test the
time-delay characteristics of protection relays
and molded-case circuit breakers. Once
the test is initiated, the current source and the
timer are automatically turned on at the next
zero-crossing point of the AC. The timer stops
when the MCCB-250 input detects a change
in the dry contact or voltage input, or detects
the removal of the test current. The test results
are then displayed in milliseconds and
fractions of cycle(s) on the unit’s back-lit LCD
screen (20 characters by 4 lines).
Current Source
The MCCB-250 has 4 current-source outputs
(5 A @ 120 Vac, 25 A @ 24 Vac, 120 A @ 6
Vac, 250 A @ 3 Vac) that conduct the test
current through the high-impedance load circuits.
Each current source can tolerate shortduration
over-loads up to 4 times the rated
current (1000 A max). This feature is used
for testing the instantaneous trip element of
molded-case circuit breakers. When using
this feature, the selected test current is displayed
on the LCD screen. When the MCCB-
250 is used as a current source, the currentfl
ow time (the current-on period) is displayed
External Current Input on the LCD screen.
The MCCB-250 also provides an external current
input (0 - 10 A). Both internal and external
current source readings can be viewed at
the same time.
Standard accessories
Part number MCCB-250 MCCB-250 and cables
Part number MCCB-250-CASE MCCB-250 shipping case
Part number MCCB-250-10FT MCCB-250 test leads - 10 foot
Part number MCCB-250-20FT MCCB-250 test leads - 20 foot
More products VANGUARD
|
DC CIRCUIT BREAKER CONTACT LOW RESISTANCE MICROOHMMETER 200A VANGUARD DMOM-200 S3
• 1 to 200A programmable test current |
|
DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-7000
• dry-contact inputs: 3 channels (9021-UC) or 6 channels (9100-UC) |
|
TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20
• accurately measure resistance values from 1 micro-ohm to 2,000 Ohms |
|
THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03 S2
• Highest ratio: 0.8 - 15,000 |
|
TRUE THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD TRI-PHASE
• Generates its own 3-phase transformer test voltage from single-phase AC or DC Power input |
|
DC AUTOMATIC CIRCUIT BREAKER CONTACT RESISTANCE MICRO-OHMMETER 200A VANGUARD AUTO-OHM 200 S3
• 1 to 200A programmable test current |
|
THREE-PHASE TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20
• accurately measure resistance from 1 micro-ohm to 2000 Ohms |
|
EHV HIGH VOLTAGE CIRCUIT BREAKER ANALYZER VANGUARD DIGITMR
• dry-contact inputs 3 dry-contact channels |
|
DIGITAL CIRCUIT BREAKER ANALYZER VANGUARD CT-8000
• dry-contact inputs 3 channels (9103-UC) or 6 channels (9104-UC) |
|
THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03
• Highest ratio: 0.8 - 15,000 |