MCF 750-N Lightweight primary injection set
High current test set up to 1300A
- 2 outputs with high current 3V(1300A) et 5V(750A)
- Low ranges to inject current up to 32A
- Injection set compact and rugged
- True RMS measurement
- Voltage generator up to 250Vac
- Measurement of ratio and direction of current transformer
OVERVIEW
- Flight Case enclosure
- Dimensions : 390 x 310 x 300 mm
- Weight : 21 kg.
SPECIFICATIONS
Power supply :
- 230V 50/60 Hz
Nominal power : 750 VA.
Max power : 2.5 kVA
Protections :
- Power supply and generator by circuit breakers
and electronic control.
Generators :
One AC current generator with voltage
function depending on load.
Current generator : 5 ranges
Output 3V : 500A/5mn ; 750A/85s ; 1300A/10s
Output 5V : 300A/5mn ; 500A/38s ; 750A/8s
Output 25A with maximum voltage 24V
Output 5A/13VA
Voltage output 250V / 2A
These specifications vary as a function of the section
of the cables used, the resistance of the contacts and
the heating of the generator in the test set. Additionally,
for correct operation it is necessary to keep the
instrument on standby for a periodthat is at least as
long as the injection period.
Cables used : 2 cables length 2m section 95 mm²
DIGITAL DISPLAY
The new control enables recording of the
trip time, threshold, and CT ratio in an internal
FLASH memory. These data can be downloaded to
a computer with windows® XP/2000/VISTA. The
data connections are USB and RS232.
Internal ammeter :
- 2 ranges 0-130 A and 130-1300 A with automatic
selection
- Precision : 1%
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- free of voltage contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999